- Title
- Estimation of physical transformer parameters from frequency response analysis
- Creator
- Mitchell, Steven D.; Welsh, James S.
- Relation
- IEEE PES Trondheim PowerTech 2011: The Power of Technology for a Sustainable Society. Proceedings of the IEEE PES Trondheim PowerTech 2011: The Power of Technology for a Sustainable Societ (Trondheim, Norway 19 - 23 June, 2011)
- Publisher Link
- http://dx.doi.org/10.1109/PTC.2011.6019187
- Publisher
- Institute of Electrical and Electronics Engineers (IEEE)
- Resource Type
- conference paper
- Date
- 2011
- Description
- The wideband frequency response of a power transformer will yield a signature unique to its mechanical geometry. A change in the frequency response can be indicative of winding deformation. Frequency Response Analysis (FRA) is a diagnostic tool used to monitor frequency response changes. The aim of this paper is to facilitate FRA interpretation through the development of a three phase transformer model that is based on the estimation of physical parameters. The paper will demonstrate the applicability of the model by using FRA data sets of a 1.3 MVA distribution transformer and assessing the accuracy of key parameter estimates.
- Subject
- frequency response; parameter estimation; power transformers; transformer windings
- Identifier
- http://hdl.handle.net/1959.13/921000
- Identifier
- uon:9240
- Identifier
- ISBN:9781424484195
- Language
- eng
- Full Text
- Reviewed
- Hits: 1099
- Visitors: 1397
- Downloads: 399
Thumbnail | File | Description | Size | Format | |||
---|---|---|---|---|---|---|---|
View Details Download | ATTACHMENT02 | Author final version | 295 KB | Adobe Acrobat PDF | View Details Download |